PAD100-ZM
Zone Module
This addressable zone monitoring module uses one SLC address to monitor two Class B circuits or one Class A circuit.
OVERVIEW
This addressable zone monitoring module uses one SLC address to monitor two Class B circuits or one Class A circuit.
The module requires a supervised 24 VDC auxiliary power supply, and the initiating device circuit can be configured for Class A or Class B operation through an onboard switch. A built-in LED provides visual indication of normal communication and device activation status.
KEY FEATURES
- Uses one SLC address
- Monitors two Class B circuits or one Class A circuit
- Requires supervised 24 VDC auxiliary power
- Supports selectable Class A or Class B IDC configuration
- Built-in LED status indication
SPECIFICATIONS
- Operating Voltage
- 24.0V
- Operating Temperature Range
- 32 to 120ºF (0 to 49ºC)
- Max no. of Module per Loop
- 127 units